|
A recommended reference is the:
Photovoltaic Power Systems and the 2005 National Electrical Code:
Suggested Practices
Sandia National Laboratories
John Wiles
NTIS Order Number: PB2005-108229
Available in CD, Microfiche, Downloadable, and Color Document.
|
Available from:
U.S. Department of Comerce
National Technical Information Service
5285 Port Royal Rd
Springfiled, VA 22161
Telephone: (800) 53-6847
Fax: (865) 605-6900
e-mail: orders@ntis.fedworld.gov
web: http://www.ntis.gov/search/results.asp?loc=3-0-0 |
A few short excerpts from this reference follow:
PHOTOVOLTAIC MODULES
Numerous PV module manufacturers offer listed modules. In some cases
(building integrated or architectural structures), unlisted PV modules
have been installed, but these installations should have been approved
by the local authority having jurisdiction (electrical inspector).
MODULE MARKING
Certain electrical information must appear on each module. The information on the factory-installed label shall include the following items [690.51]:
Information Supplied by Manufacturer
- Polarity of output terminals or leads
- Maximum series fuse for module protection
- Rated open-circuit voltage
- Rated operating voltage
- Rated operating current
- Rated short-circuit current
- Rated maximum power
- Maximum permissible system voltage [690.51]
Although not required by the NEC, the
temperature rating of the module terminals and conductors are given to
determine the temperature rating of the insulation of the conductors
and how the ampacity of those conductors must be
derated for temperature [11O.14(C)]. While module terminals are usually
rated for 90°C, most other terminals throughout the PV system will have
terminals rated only for 60°C or 75°C. These terminal temperatures may
significantly affect conductor ampacity.
Note: Other critical
information, such as mechanical installation instructions, grounding
requirements, tolerances of indicated values of Isc, Voc and Pmax, and
statements on artificially concentrated sunlight are contained in the
installation and assembly instructions for the module.
PHOTOVOLTAIC ARRAY DISCONNECTS
Article 690 requires all current-carrying conductors from the PV power source or other power source to have disconnect provisions. This provision includes the grounded conductor, if any [690 III]. Ungrounded conductors must have a switch or circuit breaker disconnect [690.13, IS, 17]. Grounded conductors
which normally remain connected at all times, may have a bolted
disconnect (terminal or lug) that can be used for service operations
and for meeting the NEC requirements. Disconnect switches must not open
grounded conductors [690.13]. Grounded conductors of faulted source
circuits in roof-mounted dc PV arrays on dwellings are allowed to be
automatically interrupted as part of ground-fault protection
requirements in 690.5. [690.13]
In an ungrounded 12-volt PV system (as allowed by [690.41]), both positive and negative conductors must be switched, since both are ungrounded. Since all systems must have
an equipment-grounding system, costs may be reduced and performance
improved by grounding 12-volt systems and using one-pole disconnects on
the remaining ungrounded conductor.
Ungrounded systems operating at higher voltages, as will be allowed by the 2005 NEC in
690.35, will also require switched disconnects and overcurrent
protection in all of the circuit conductors since both the positive and
negative circuit conductors will be ungrounded. See Appendix L for
additional discussions of ungrounded PV systems.
INVERTERS
Inverters can have stand-alone, utility-interactive, or combined capabilities.
The
ac output wiring is not significantly different from the ac wiring in
residential and commercial construction, and the same general
requirements of the Code apply. In the case of utility-interactive
systems and combined systems, ac power may flow through circuits in
both directions. This two-way current flow will normally require
overcurrent devices at both ends of the circuit.
The dc input
wiring associated with stand-alone or hybrid inverters is the same as
the wiring described for batteries. Most of the same rules apply;
however, the calculation of the dc input current needs special
consideration since the NEC does not take into consideration
some of the finer points required to achieve the utmost in reliability.
Appendix' F discusses these special requirements in greater detail.
The
dc input wiring associated with utility-interactive inverters is
similar, in most cases, to the wiring in PV source and output circuits.
Inverters
with combined capabilities will have both types of dc wiring:
connections to the batteries and connections to the PV modules.
SUGGESTED PRACTICES
APPENDIX E:
Example Systems
The
systems described in this appendix and the calculations shown are
presented as examples only. The calculations for conductor sizes and
the ratings of overcurrent devices are based on the requirements of the
National Electrical Code (NEC) and on UL Standard 1703 which
provides instructions for the installation of UL-Listed PV modules.
Local codes and site-specific variations in irradiance, temperature,
and module mounting, as well as other installation particularities,
dictate that these examples should not be used without further
refinement. Tables 310.16 and 310.17 from the NEC provide the ampacity data and temperature derating factors.
CABLE SIZING AND OVERCURRENT PROTECTION
The procedure presented below for cable sizing and overcurrent protection of that cable is based on NEC requirements
in Sections 690.9, 690.8, 110. 14(C), 21O.20(A), 215.2, 215.3, 220.10,
240.3(B), and 240.6(A). See Appendix I for a slightly different method
of making ampacity calculations based on the same requirements.
1.
Circuit Current. For circuits carrying currents from PV modules,
multiply the short-circuit current by 125% and use this value for all
further calculations. For PV circuits in the following examples, this
is called the CONTINUOUS CURRENT calculation. In the Code, this
requirement has been included in Section 690.8, but also remains in UL
1703. This multiplier should not be applied twice. For dc and ac
inverter circuits in PV systems, use the rated continuous currents. AC
and dc load circuits should follow the requirements of Sections 210,
220, and 215.
2. Overcurrent Device Rating. The overcurrent
device must be rated at 125% of the current determined in Step 1. This
is to prevent overcurrent devices from being operated at more than 80%
of rating. This calculation, in the following examples, is called the
80% OPERATION.
3. Cable Sizing. Cables shall have a 30°C ampacity of 125% of the current
determined in Step 1 to ensure proper operation of connected
overcurrent devices. There are no additional deratings applied with
this calculation.
4. Cable Derating. Based on the
determination of Step 3 and the location of the cable (raceway or
free-air), a cable size and insulation temperature rating (60, 75, or
90°C) are selected from the NEC Ampacity Tables 310.16 or
310.17. Use the 75°C cable ampacities to get the size, then use the
ampacity from the 90°C column-if needed-for the deratings. This cable
is then derated for temperature, conduit fill, and other requirements.
The resulting derated ampacity must be greater than the value found in
Step 1. If not greater, then a larger cable size or higher insulation
temperature must be selected. The current in Step 3 is not used at this
point to preclude over sizing the cables.
5. Ampacity
vs. Overcurrent Device. The derated ampacity of the cable selected in
Step 4, must be equal to or greater than the overcurrent device rating
determined in Step 2 [240.4]. If the derated ampacity of the cable is
less than the rating of the overcurrent device, then a larger cable
must be selected. The next larger standard size overcurrent device may
be used if the derated cable ampacity falls between the standard
overcurrent device sizes found in NEC Section 240.6.
Note: This step may result in a larger conductor size than that determined in Step 4.
6.
Device Terminal Compatibility. Since most overcurrent devices have
terminals rated for use with 75°C (or 60°C) cables, compatibility must
be verified [110.3(8)]. If a 90°C-insulated cable was selected in the
above process, the 30°C ampacity of the same size cable with a 75°C (or
60°C) insulation must be greater than or equal to the current found in
Step 1
[110 .14( C)]. This ensures that the cable will
operate at temperatures below the temperature rating of the terminals
of the overcurrent device. If the overcurrent device is located in an
area with ambient temperature higher than 30°C, then the 75°C (or 60°C)
ampacity must also be derated [11O.3(B)].
The entire
National Electrical Code® can be purchased from the National Fire Protection Association (NFPA) at their web site - www.NFPA.org