Schneider (Xantrex) XW6048-120/240-60, 120/208-60 Inverter

- Schneider (Previously Xantrex) XW6048-120/240-60 1 or 3-Phase Hybrid Inverter Charger
Now you can order the XW 6048 Inverter/Charger that has the flexibility to configure for single and three phase applications! The XW 6048 (part number 865-1000-01) is a standard split phase inverter 120:240V and can now be used in one of three ways: - Split phase inverter
- Single phase inverter
- Three phase inverter (three inverters configured in single phase and run together as three phase)
The configuration for the single or three phase applications (part number 865-1000-01 only) is done in the field with these three simple steps*: - 1). Installation of jumpers to reconfigure the transformer to 120V (jumpers provided)
- 2). Download and install the new XW 6048-1000-01 firmware version for 120V operation (click here)
- 3). Set parameters for single or three phase configuration using the XW SCP
* Please read configuration information prior to configuring the standard split phase XW 6048 part number 865-1000-01 to a 120V single-phase, setting up an XW single-phase system, or setting up an XW three-phase system (120:208V) Please note: Xantrex is unable to exchange any current inventory or current orders of the model 865-1000 with the new 865-1000-01. The NEXT generation inverter/charger for renewable energy systems and backup power applications Xantrex brings the next generation of inverter/charger to market, with the XW Hybrid Inverter/Charger, the heart of the XW System. The XW Hybrid Inverter/Charger (XW) is a true sine wave, 120/240-volt AC, split-phase, inverter/charger that incorporates a DC to AC inverter, a battery charger, and an AC auto-transfer switch. It is the foundation for battery- based residential and commercial applications up to 18 kilowatts (kW). Capable of being grid-interactive or grid-independent, the XW can operate with generators and renewable energy sources to provide full time or backup power. Description Designed with consultation and input from industry experts, dealers, and installers, the XW sets a new standard for battery-based inverter/chargers. Integrating the best features available in the market, innovative new features by Xantrex and balance-of-systems components, the XW Hybrid Inverter/Charger’s design makes installation quicker and easier. The XW offers high efficiency and unprecedented surge capacity to maximize the owner’s return on investment. No other inverter/charger looks or performs like the XW. Features - True sine wave output
- 120/240 volt AC spilt-phase operation
- Dual AC inputs
- Capability to work with two-wire and three-wire generator starting systems
- Integrated design to minimize external balance-of-system components
- XanBusTM-enabled network communication
- Certified to UL1741 and CSA for utility-interactive applications
- Unprecedented surge capacity
- Efficient, power factor corrected, high-current, multistage battery charging
Electrical Specifications Model XW6048-120/240-60L Continuous output power: 6000 Watts Surge rating (10 seconds): 12000 Watts Surge current: L-L: 40 Arms (20 sec) L-N: 105 Arms (7 sec) Waveform: True sine wave Low-load efficiency: 95% Idle consumption - search mode< 8 Watts AC connections: AC1 (Grid), AC2 (Generator) AC voltage: 120/240 Vac split-phase AC input breaker: 60 A two-pole Utility interactive: Yes CEC weighted efficiency: 92.5% CEC power rating: 5752 Watts AC input voltage range (bypass/charge mode) L-N: 80-150 Vac (120 V nominal); L-L: 160-270 Vac (240 V nominal) AC input frequency range (bypass/charge mode) 55-65 Hz (default); 44-70 Hz (allowable) AC1 voltage range – Sell mode L-N: 108-130 +/- 1.5 Vac; L-L: 214 - 260 +/- 3.0 Vac (automatically adjusts when entering Sell mode)* AC1 frequency range – Sell mode: 59.4 - 60.4 +/- 0.05 Hz (automatically adjusts when entering Sell mode)* AC output voltage: L-N: 120 Vac +/- 3%; L-L: 240 Vac +/- 3% AC output frequency: 60.0 +/-0.1 Hz DC current at rated power: 130 Amps Total harmonic distortion: < 5% Automatic transfer relay: 60 Amps Typical transfer time: 8 ms DC input voltage (nominal): 50.4 Vdc DC input voltage range: 44 - 64 Vdc Maximum continuous charge rate: 100 Amps Efficiency at maximum charge rate: 89.4% Power factor corrected charging: 0.98 Emissions: FCC Class B Multiple-unit configurations: Up to three parallel units in 120/240-volt split- phase configuration Auxiliary relay output: 0-12 Vdc, maximum 250 mA DC Non-volatile memory: Yes System network Xanbus™ (publish-subscribe network, no need for hubs or special cards) Mechanical Specifications Mounting: Wall mount, backplate included Inverter dimensions (H x W x D) 23 x 16 x 9” (580 x 410 x 230 mm) Inverter weight: 125 lb (57 kg) Display panel: Status LEDs indicate AC In status, faults/warnings, equalize mode, battery level. Three-character display indicates output power or charge current, fault/warning codes. On/Off and equalize buttons Battery temperature sensor: Included Standard warranty: Five years Part number: 865-1000 Environmental Specifications Enclosure type NEMA Type 1 – Indoor (sensitive electronic components sealed inside enclosure) Operational temperature range: -13°F to 158°F (-25°C to 70°C) Accessories Remote display Optional XW System Control Panel monitors and configures all devices connected to Xanbus™ Network Generator support: Optional XW Automatic Generator Start module connects to Xanbus™ Network. Automatically activates generator to recharge depleted battery bank or assist inverter with heavy loads Power distribution & panel conduit boxes: Optional balance-of-systems components for NEC compliant installations, includes pre-wired AC and DC circuit breakers, bus barsand multiple knockouts for conduit and additional breakers Regulatory Approval UL 1741 1st Edition: 2005 Version CSA 107.1-01 Specifications subject to change without notice. Optional Accessories - XW Power Distribution Panel 865-1015
- XW Connection Kit for Second Inverter 865-1020
- XW Conduit Box 865-1025
- XW Solar Charge Controller 865-1030
- XW System Control Panel 865-1050
- XW Automatic Generator Start 865-1060
Xantrex expects the system designer to use the XW Charge Controller with their inverters. Their sizing tools assume the XW Charge Controller. Most importantly, Xantrex handles the Ground Fault Protection (required by National Electric Code 2008 in all systems) in the charge controller. If you do not use the Xantrex XW Charge Controller then the GFP must be handled in a different way. Shipping dimensions: 28" x 22.25" x 10.5" (711 x 565 x 267 mm) Shipping weight: 132 lb (60 kg)
- No information available
-
Length: 28"
Width: 22.25"
Height: 10.5"
Weight: 181 lbs
-